mirror of
https://github.com/OpenLogics/MewtocolNet.git
synced 2025-12-06 03:01:24 +00:00
Update README.md
This commit is contained in:
142
README.md
142
README.md
@@ -1,39 +1,137 @@
|
|||||||
# MewtocolNet
|
# MewtocolNet
|
||||||
A Mewtocol protocol library to interface with Panasonic PLCs over TCP/Serial.
|
A Mewtocol protocol library to interface with Panasonic PLCs over TCP/Serial.
|
||||||
|
|
||||||
|
# Support
|
||||||
|
|
||||||
|
> This library was only tested with a few PLCs, other types that support the Panasonic Mewtocol protocol might work.
|
||||||
|
> Use at your own risk, others might follow with community feedback
|
||||||
|
|
||||||
|
|PLC Type|Supported|Tested|
|
||||||
|
|--------|---------|------|
|
||||||
|
FPX C14 |✔ |✔ |
|
||||||
|
FPX C30 |✔ |✔ |
|
||||||
|
FPX-H C14|✔ |✔ |
|
||||||
|
FPX-H C30|✔ |✔ |
|
||||||
|
FP Sigma |✔ |❌ |
|
||||||
|
|
||||||
|
Where is the RS232/Serial support
|
||||||
|
|
||||||
|
> Support for the serial protocol will be added soon, feel free to contribute
|
||||||
|
|
||||||
|
|
||||||
# Usage
|
# Usage
|
||||||
|
|
||||||
1. Connecting to a PLC
|
## Connecting to a PLC
|
||||||
|
|
||||||
|
Connecting to a PLC is as simple as
|
||||||
|
|
||||||
```C#
|
```C#
|
||||||
//Create a new interface class with your PLCs IP address and port
|
//attaching a logger
|
||||||
MewtocolInterface interf = new MewtocolInterface("127.0.0.1", 9094);
|
Logger.LogLevel = LogLevel.Verbose;
|
||||||
|
Logger.OnNewLogMessage((date, msg) => {
|
||||||
|
Console.WriteLine($"{date.ToString("HH:mm:ss")} {msg}");
|
||||||
|
});
|
||||||
|
|
||||||
//Setup the dataregisters of the PLC you want to read
|
//setting up a new PLC interface
|
||||||
interf.AddRegister<short>("Test Integer",1204);
|
MewtocolInterface interf = new MewtocolInterface("10.237.191.3");
|
||||||
interf.AddRegister<string>(1101, 4);
|
|
||||||
|
|
||||||
//attaches an auto reader that polls the registers
|
await interf.ConnectAsync();
|
||||||
interf.WithPoller();
|
```
|
||||||
|
|
||||||
//triggers when a dataregister changes its value
|
You can also use the callbacks of the `ConnectAsync()` method to do something after the initial connection establishment.
|
||||||
interf.RegisterChanged += (o) => {
|
|
||||||
Console.WriteLine($"DT{o.MemoryAdress} {(o.Name != null ? $"({o.Name}) " : "")}changed to {o.GetValueString()}");
|
|
||||||
};
|
|
||||||
|
|
||||||
//Connects to the PLC asynchronous and invokes connected or failed
|
```C#
|
||||||
await interf.ConnectAsync(
|
await interf.ConnectAsync(
|
||||||
(plcinf) => {
|
//PLC connected
|
||||||
|
(plc) => {
|
||||||
Console.WriteLine("Connected to PLC:\n" + plcinf.ToString());
|
if(plcinf.OperationMode.RunMode)
|
||||||
|
Console.WriteLine("PLC is in RUN");
|
||||||
//read back a register value
|
|
||||||
var statusNum = (NRegister<short>)interf.Registers[1204];
|
|
||||||
Console.WriteLine($"Status num is: {statusNum.Value}");
|
|
||||||
|
|
||||||
},
|
},
|
||||||
|
//Connection failed
|
||||||
() => {
|
() => {
|
||||||
Console.WriteLine("Failed connection");
|
Console.WriteLine("PLC failed to connect");
|
||||||
}
|
}
|
||||||
);
|
);
|
||||||
```
|
```
|
||||||
|
## Reading data registers / contacts
|
||||||
|
|
||||||
|
- Create a new class that inherits from `RegisterCollectionBase`
|
||||||
|
|
||||||
|
```C#
|
||||||
|
public class TestRegisters : RegisterCollectionBase {
|
||||||
|
|
||||||
|
//corresponds to a R100 boolean register in the PLC
|
||||||
|
[Register(100, RegisterType.R)]
|
||||||
|
public bool TestBool1 { get; private set; }
|
||||||
|
|
||||||
|
//corresponds to a XD input of the PLC
|
||||||
|
[Register(RegisterType.X, SpecialAddress.D)]
|
||||||
|
public bool TestBoolInputXD { get; private set; }
|
||||||
|
|
||||||
|
//corresponds to a DT7012 - DT7013 as a 32bit time value that gets parsed as a timespan (TIME)
|
||||||
|
//the smallest value to communicate to the PLC is 10ms
|
||||||
|
[Register(7012)]
|
||||||
|
public TimeSpan TestTime { get; private set; }
|
||||||
|
|
||||||
|
//corresponds to a DT1101 - DT1104 string register in the PLC with (STRING[4])
|
||||||
|
[Register(1101, 4)]
|
||||||
|
public string TestString1 { get; private set; }
|
||||||
|
|
||||||
|
}
|
||||||
|
```
|
||||||
|
|
||||||
|
- Connect to the PLC and attach the register collection and logger
|
||||||
|
- attach an automatic poller by chaining `.WithPoller()` after the register attachment
|
||||||
|
|
||||||
|
```C#
|
||||||
|
//attaching a logger
|
||||||
|
Logger.LogLevel = LogLevel.Verbose;
|
||||||
|
Logger.OnNewLogMessage((date, msg) => {
|
||||||
|
Console.WriteLine($"{date.ToString("HH:mm:ss")} {msg}");
|
||||||
|
});
|
||||||
|
|
||||||
|
//setting up a new PLC interface and register collection
|
||||||
|
MewtocolInterface interf = new MewtocolInterface("192.168.115.3");
|
||||||
|
TestRegisters registers = new TestRegisters();
|
||||||
|
|
||||||
|
//attaching the register collection and an automatic poller
|
||||||
|
interf.WithRegisterCollection(registers).WithPoller();
|
||||||
|
|
||||||
|
await interf.ConnectAsync(
|
||||||
|
(plcinf) => {
|
||||||
|
//reading a value from the register collection
|
||||||
|
Console.WriteLine($"Time Value is: {registers.TestTime}");
|
||||||
|
}
|
||||||
|
);
|
||||||
|
```
|
||||||
|
- Your properties are getting automatically updated after the initial connection
|
||||||
|
|
||||||
|
> Note! this is not your only option to read registers, see here
|
||||||
|
|
||||||
|
## Writing data registers / contacts
|
||||||
|
|
||||||
|
### Synchronous
|
||||||
|
|
||||||
|
Sets the register without feedback if it was set
|
||||||
|
|
||||||
|
```C#
|
||||||
|
//inverts the boolean register
|
||||||
|
interf.SetRegister(nameof(registers.TestBool1), !registers.TestBool1);
|
||||||
|
|
||||||
|
//set the current second to the PLCs TIME register
|
||||||
|
interf.SetRegister(nameof(registers.TestTime), TimeSpan.FromSeconds(DateTime.Now.Second));
|
||||||
|
|
||||||
|
//writes 'Test' to the PLCs string register
|
||||||
|
interf.SetRegister(nameof(registers.TestString1), "Test");
|
||||||
|
```
|
||||||
|
|
||||||
|
You can also set a register by calling its name directly (Must be either in an attached register collection or added to the list manually)
|
||||||
|
|
||||||
|
### Asynchronous
|
||||||
|
|
||||||
|
Sets the register waiting for the PLC to confirm it was set
|
||||||
|
|
||||||
|
```C#
|
||||||
|
//inverts the boolean register
|
||||||
|
interf.SetRegisterAsync(nameof(registers.TestBool1), !registers.TestBool1);
|
||||||
|
```
|
||||||
|
|||||||