# Open Questions - What is the HW information byte for? - What are the last bytes of the EXRT message for? # Actual Readouts | PLC TYPE | CPU Code | Machine Code | HW Information| |--------------|--------------|--------------|---------------| | FPX C14 R | 20 | 70 | 02 | | FPX C30 T | 20 | 77 | 02 | | FPX-H C14 R | 20 | A0 | 01 | | FPX-H C30 T | 20 | A5 | 01 | ## FPX 16k C14R Actual Response Examples ### %EE$RT |Reponse Byte|Description| |------------|-----------| | 20 | Model code | | 25 | Version | | 16 | Prog capacity | | 80 | Op mode | | 00 | Link unit | | E1 | Error flag | | 2D00 | Self diag error | ### %EE$EX00RT Normal Operation |Reponse Byte|Description| |------------|-----------| | 00 | Extended mode | 32 | Data item count | 70 | Machine type | 00 | Version (Fixed to 00) | 16 | Prog capacity in K | 80 | Operation mode / status | 00 | Link unit | E1 | Error flag | 2D00 | Self diag error | 50 | Version | 02 | Hardware information | 0 | Number of programs | 4100 | Program size BCD | 1600 | Header size (no. of words) bcd | 1604 | System register size | 96230000001480004 | ? ### %EE$EX00RT with error |Reponse Byte|Description| |------------|-----------| | 00 | Extended mode | 32 | Data item count | 70 | Machine type | 00 | Version (Fixed to 00) | 16 | Prog capacity in K | 81 | Operation mode / status | 00 | Link unit | 60 | Error flag | 0000 | Self diag error | 50 | Version | 02 | Hardware information | 0 | Number of programs | 4100 | Program size BCD | 1600 | Header size (no. of words) bcd | 1604 | System register size | 96230000001480004 | ? What are the last bytes? FP-X 16k C14R 96 23 00 00 00 14 80 00 4 FP-X 32k C30T/P 96 23 00 00 00 14 80 00 4 FP-XH 32k C30T/P 96 23 00 00 00 40 00 00 4 FP-XH 16k C14R 96 23 00 00 00 40 00 00 4 ## FP-XH 16k C14R Actual Response Examples ### %EE$RT |Reponse Byte|Description| |------------|-----------| | 20 | Model code | | 16 | Version | | 16 | Prog capacity | | 81 | Op mode | | 00 | Link unit | | 60 | Error flag | | 0000 | Self diag error |