Open Questions
- What is the HW information byte for?
- What are the last bytes of the EXRT message for?
Mewtocol Init
| PLC TYPE | CPU Code | Machine Code | HW Information |
|---|---|---|---|
| FPX C14 R | 20 | 70 | 02 |
| FPX C30 T | 20 | 77 | 02 |
| FPX-H C14 R | 20 | A0 | 01 |
| FPX-H C30 T | 20 | A5 | 01 |
FPX 16k C14R Actual Response Examples
%EE$RT
| Reponse Byte | Description |
|---|---|
| 20 | Model code |
| 25 | Version |
| 16 | Prog capacity |
| 80 | Op mode |
| 00 | Link unit |
| E1 | Error flag |
| 2D00 | Self diag error |
%EE$EX00RT Normal Operation
| Reponse Byte | Description |
|---|---|
| 00 | Extended mode |
| 32 | Data item count |
| 70 | Machine type |
| 00 | Version (Fixed to 00) |
| 16 | Prog capacity in K |
| 80 | Operation mode / status |
| 00 | Link unit |
| E1 | Error flag |
| 2D00 | Self diag error |
| 50 | Version |
| 02 | Hardware information |
| 0 | Number of programs |
| 4100 | Program size BCD |
| 1600 | Header size (no. of words) bcd |
| 1604 | System register size |
| 96230000001480004 | ? |
What are the last bytes?
FP-X 16k C14R 96 23 00 00 00 14 80 00 4
FP-X 32k C30T/P 96 23 00 00 00 14 80 00 4
FP-XH 32k C30T/P 96 23 00 00 00 40 00 00 4
FP-XH 16k C14R 96 23 00 00 00 40 00 00 4
FP-XH 16k C14R Actual Response Examples
%EE$RT
| Reponse Byte | Description |
|---|---|
| 20 | Model code |
| 16 | Version |
| 16 | Prog capacity |
| 81 | Op mode |
| 00 | Link unit |
| 60 | Error flag |
| 0000 | Self diag error |
FP-X0 2.5k L14,L30
%EE$RT
| Reponse Byte | Description |
|---|---|
| 72 | Model code |
| 12 | Version |
| 02 | Prog capacity |
| 82 | Op mode |
| 00 | Link unit |
| 00 | Error flag |
| 0000 | Self diag error |
%EE$EX00RT
| Reponse Byte | Description |
|---|---|
| 00 | Extended mode |
| 32 | Data item count |
| 72 | Machine type |
| 00 | Version (Fixed to 00) |
| 02 | Prog capacity in K |
| 82 | Operation mode / status |
| 00 | Link unit |
| 00 | Error flag |
| 0000 | Self diag error |
| 23 | Version |
| 01 | Hardware information |
| 0 | Number of programs |
| 4100 | Program size BCD |
| 0301 | Header size (no. of words) bcd |
| 2819 | System register size |
| 0000001480004 | ? |
FP0 2.7k C10,C14
%EE$RT
| Reponse Byte | Description |
|---|---|
| 05 | Model code |
| 12 | Version |
| 03 | Prog capacity |
| 82 | Op mode |
| 00 | Link unit |
| 00 | Error flag |
| 0000 | Self diag error |
%EE$EX00RT
| Reponse Byte | Description |
|---|---|
| 00 | Extended mode |
| 32 | Data item count |
| 40 | Machine type |
| 00 | Version (Fixed to 00) |
| 03 | Prog capacity in K |
| 82 | Operation mode / status |
| 00 | Link unit |
| 00 | Error flag |
| 0000 | Self diag error |
| 23 | Version |
| 01 | Hardware information |
| 0 | Number of programs |
| 4100 | Program size BCD |
| 0301 | Header size (no. of words) bcd |
| 2819 | System register size |
| 20130000080070004 | ? |
Mewtocol-7 Com
Getting the status of the plc
%EE#RT
Normal plc would return the default, see above.
The FP7 series returns:
%EE$RT0000000100000000
This indicates that the device uses the Mewtocol 7 format
When trying to use EXRT the FP7 returns not supported
[R] %EE#EX00RT00
[S] %EE!42
Then request the status from the PLC using Mewtocol 7
[R] >@EEE00#30STRD00
[O] >@EEE00$30STRD
| Reponse Byte | Description |
|---|---|
| 00 | Read status (always 0) |
| 07 | series code: 7 = FP7 |
| 10 | model code: 3 = CPS41E, 4 = CPS31E, 5 = CPS31, 6 = CPS41ES, 7 = CPS31ES, 8 = CPS31S, 9 = CPS21, 10 = ElC500 |
| 0000 | user special order code (Not important) |
| 0453 | latest cpu version = 4.53 |
| 0453 | communication cpu version = 4.53 |
| 0453 | operation cpu version = 4.53 |
| 01 | op mode = 4.53 |
| 00 | error flag |
| 0000 | self diag error |
| 00 | sd card information |